Applications
- Vessels, piping, valves
- Food processing industry
- Frost protection and temperature maintenance on pumps, etc.
Technical Information
- Insulation: Silicone
- Protective braid: Copper
- Outer jacket: Silicone
- Nominal temperature: 200 °C
- Moisture proof
- Bending radius, min.: 30 mm
- Bus wire cross section: 2 x 1.5 mm²
- Nominal voltage: 230 V AC/DC
- Installation temp., min.: -60 °C
- Start-up temp., min.: -60 °C
- Nominal output: 10 / 20 / 30 / 40 W/m
ELP/Si-F-B up to 200 °C
Applications
- Vessels, piping, valves
- Food processing industry
- Frost protection and temperature maintenance on pumps, etc.
- Filter heating systems
Technical Information
- Insulations: Silicone
- Protective braid: Copper/zinc
- Outer jacket: Silicone
- Nominal voltage: 230 V AC/DC or 400 V AC/DC
- Dimensions: 6.5 x 10.5 mm
- Permissible ambient temperature: -70…+200 °C
- Bending radius, min.: 30 mm
- Bus wire cross section: 2 mm²
- Installation temp., min.: -70 °C
- Start-up temp., min: -70 °C
- Nominal output: 20 / 30 / 40 W/m
ELP/Si-F-BOT up to 200 °C
Applications
- Vessels, piping, valves
- Food processing industry
- Frost protection and temperature maintenance on pumps, etc.
- Filter heating systems
Technical Information
- Insulations: Silicone
- Protective braid: Copper/zinc
- Outer jacket: Fluoropolymer
- Nominal voltage: 230 V AC/DC or 400 V AC/DC
- Dimensions: 7 x 10.5 mm
- Permissible ambient temperature: -70…+200 °C
- Bending radius, min.: 30 mm
- Bus wire cross section: 2 mm²
- Installation temp., min.: -70 °C
- Start-up temp., min: -70 °C
- Nominal output: 20 / 30 / 40 W/m
ELP/PFA up to 260 °C
Applications
- Vessels, piping, valves
- Building construction
- Food processing industry
- Paper industry
- Hazardous area applications
Technical Information
- Insulations: Fluoropolymer
- Protective braid: Nickel-plated copper
- Outer jacket: Fluoropolymer
- Nominal temperature: 260 °C
- Moisture proof
- Bending radius, min.: 25 mm
- Bus wire cross section: 2 x 1.5 mm²
- Nominal voltage: 230 V AC/DC
- Installation temp., min.: -45 °C
- Start-up temp., min.: -45 °C
- Manufactured according to: DIN VDE 0721-52, EN 62395-1; 2007-05
- Certificates: 12ATEX1438U, IECEx EPS 12.0009U
- Classification: II 2G Ex e IIC Gb II 2D Ex tb IIIC Db
- Nominal output: 15 / 30 / 45 / 60 W/m
ELP/FEP up to 200 °C
Applications
- Vessels, piping, valves
- Building construction
- Food processing industry
- Paper industry
Technical Information
- Insulations: Fluoropolymer
- Protective braid: Nickel-plated copper
- Outer jacket: Fluoropolymer
- Nominal temperature: 200 °C
- Moisture proof
- Bending radius, min.: 25 mm
- Bus wire cross section: 2 x 1.5 mm²
- Nominal voltage: 230 V AC/DC
- Installation temp., min.: -45 °C
- Start-up temp., min.: -45 °C
- Manufactured according to: DIN VDE 0721-52, EN 62395-1; 2007-05